Click for new scientific resources and news about Corona[COVID-19]

Paper Information

Journal:   TABRIZ JOURNAL OF ELECTRICAL ENGINEERING   SUMMER 2016 , Volume 46 , Number 2 (76); Page(s) 197 To 208.
 
Paper: 

OPTIMAL PLACEMENT OF CURRENT MEASUREMENT UNITS FOR ACCURATE AND SMART FAULT LOCATION PURPOSE

 
 
Author(s):  GORGANI FIROUZJAH K.*
 
* FACULTY OF ENGINEERING AND TECHNOLOGY, UNIVERSITY OF MAZANDARAN, BABOLSAR, IRAN
 
Abstract: 

This paper presents a fault location technique for transmission lines with minimum current measurement units. The proposed method used proper current ratios to find fault locations based on both The venin theory in faulty power networks and calculation of short circuit currents in each branch. These current ratios are extracted based on lowest sensitivity to The venin impedance variations of the network. Proposed algorithm compares current ratios in offline calculations with associated values collected by measurements with a lookup table mechanism. A similarity measure algorithm can find location of the fault including line number and the distance. A multi-objective optimization problem using Bees Algorithm (BA) is used to search monitoring points with minimum possible current measurements. Accuracy of the proposed algorithm is evaluated in a widely used multi-machine network of Western Systems Coordinating Council (WSCC).

 
Keyword(s): FAULT LOCATION, CURRENT MEASUREMENT UNIT-O, SIMILARITY MEASURE
 
References: 
  • ندارد
 
  Persian Abstract Yearly Visit 61
 